BACnetTStatUser’sManualRev1.1,7/28/11 Page|4
4. MountthePlate‐Dressthewiresthroughthecenterwindowonthebackplateandinstall
mountingscrews.Tightenscrewstoensuretheplateismountedsecurely,butdonotover
tightenandwarpthebackplate.
2.2Wiring
1. TerminatetheWireConnectionsCutoffexcesswire,dresswireflushtothebackpaneland
strip1/4”ofinsulationtoexposeconductor.InsertandtightenusingtheWireTerminations
diagram.
2. ConnectionDescriptions:
ZONE+

Formountingaremotetemperaturesensor,setJumper
ZONE
 J1/2totop&middleandSENSSPOTtooffonfrontpanel
SUPPLY+

SupplyDucttemperaturesensor
SUPPLY
 
FANP+

FANProofofRuncurrenttransducer
FANP
 
MA+

24mAinputforoptionalsensor
MA24/‐
 “Onfuturemodels”
DIN+

Digitalinputforoptionalinput
DIN
 “Onfuturemodels”
AOP+

Analogoutputforadditionalcontrol
AOP
 “Onfuturemodels”
BUSD0‐

BusWirefromQuestBACnetRouterandthenonto
BUSD1+
additionalTStats
BUSC
 
R

24VACpower‐red
C

24VACcommon‐black
FANG

FanControlgreen
COOLY1

CallforCool,stage1‐yellow
COOLY2

CallforCool,stage2Blue/Orange
HEAT
W1/B
CallforHeat,stage1‐white
HEATW2

CallforHeat,stage2Varies
0

HeatPumpReversingValve‐orange
Figure2‐ConnectionDescriptions
