148 • BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Device Management-DeviceCommunicationControl-B (DM-DCC-B)
The B device responds to communication control exercised by the A device.
BACnet Service Requests Execute
DeviceCommunicationControl x
Support for requests of a limited duration is required, and support for requests
of an indefinite duration is optional.
Device Management-TimeSynchronization-B (DM-TS-B)
The B device interprets time synchronization messages from the A device.
BACnet Service Requests Execute
TimeSynchronization x
DM-TS-B compliant devices must support the Local_Time and Local_Date
properties of the Device object.
Device Management-UTCTimeSynchronization-B (DM-UTC-B)
The B device interprets time synchronization messages from the A device.
BACnet Service Requests Execute
UTCTimeSynchronization x
DM-TS-B compliant devices must support the Local_Time, Local_Date,
UTC_Offset, and Daylight_Savings_Status properties of the Device object.
Device Management-ReinitializeDevice-B (DM-RD-B)
The B device performs reinitialization requests from the A device. The op-
tional password field shall be supported.
BACnet Service Requests Execute